How to Specify Architectural Louvres

How toSpecifying Louvres on free area alone can cause serious problems:

The principle reason for using louvres is to move air. How do you know if the louvre you specify will actually deliver the air volume the engineer asked for? History has shown that sizing and specifying louvres on free area alone can cause problems for architects and owners.

When  you specify a 50% free area louvre, what are you actually getting?

The reality is that other factors also impact  airflow, not just the free area, for example Louvre frames can add resistance to airflow. Mullions, structural supports, bird screens and insect screens also reduce airflow.

A more efficient specification solution is based on the needs of the building. It is therefore important to consider the following when specifying louvres:

  • Site location and exposure
  • Severity of local (site) weather conditions
  • Location and exposure of louvres on building
  • Airflow rate and direction through louvre
  • Maximum acceptable pressure drop
  • Degree and depth of water penetration acceptable
  • Aesthetics of the building
Example NBS Style Louvre Specification

To be read with Preliminaries / General Conditions

GENERAL

110 Evidence of Performance

Certification: Provide independently certified evidence that all incorporated components comply with specified performance requirements

120 Site Dimensions

Procedure: before starting work on designated items, take site dimensions, record on shop drawings and use to ensure accurate fabrication

PRODUCTS

650 Metal Louvres

  • Manufacturer: Construction Specialties (UK) Limited, 1010 Westcott Venture Park, Westcott, Aylesbury, Bucks, HP18 0XB
  • Tel: +44 (0)1296 652800
  • Fax: +44 (0)1296 652888
  • Web: www.c-sgroup.co.uk
  • Email: info@c-sgroup.co.uk
  • Product Reference: CS 127mm Deep Storm Resistant Fixed Performance Louvre Model RSH 5700
  • Materials: Heads, Sills, Jambs and mullions to be one-piece structural aluminium members with integral caulking slot and retaining beads. Mullions shall be sliding interlock type. Blades to be one-piece aluminium extrusions with front lip gutter and multiple secondary gutters designed to catch and direct water to sill. Louvres to be supplied with 102mm high by full depth sill flashings formed from minimum 1.27mm thick aluminium. Sill flashings to have welded side panels.
  • Louvres and sill flashings to be as follows: Heads, Sills, Jambs and Mullions: Minimum of 1.91mm.  Fixed blades: 1.52mm
  • Fabrication: Louvres to be mechanically assembled using stainless steel or aluminium fasteners
  • Finish: Polyester Powder Coating – Colour: RAL 9003
  • Size: As per elevation drawings and louvre schedule
  • Number of louvre banks: Integrated slim-line double bank to give tangential separation
  • Louvre blade pitch and angle: 50mm at Zero Degrees
  • Performance Requirements: Louvres to be extruded to give an aerodynamically efficient profile to create tangential separation of water in airflow. Louvre to be mechanically fastened within extruded framing sections complete with integral channels to achieve maximum drainage. The system shall achieve a minimum Discharge Loss Coefficient of 0.320 and when tested in accordance with the principles of BS EN 13030:2001 (at 13m/s wind speed) will achieve the following Penetration Classes: A at 1m/s,  A at 3m/s and C at 5m/s
  • Blanking Panels: As per drawings, schedules and M&E requirements
  • Installation: Louvre to be installed by competent installer, strictly in accordance with manufacturer’s instructions back to primary steel structure

If you need assistance creating your Louvre Specification, contact the experts on +44 (0)1296 652800 or email: sales@c-sgroup.co.uk.

Filed Under: Blog Tagged With: Louvres

Louvres

2016 Louvre Brochure
What's in the brochure
  • - Industry Leading Products
  • - Innovative New Design Options
  • - Detailed Technical Information
  • - Louvre Specification Guidance

1300 272 602
sales@c-sgroup.com.au
Order a Sample
Request an Estimate
Get Technical Help

Related Posts
  • Intro to Louvre Performance Testing
  • A Brief Intro to Architectural Louvres
  • Building and Architectural Louvres Explained
  • Class A: Not all Weather or Performance Louvres are the same
  • How To Compare Architectural Louvre Models
  • How To Correctly Specify Building & Architectural Louvres

Menu

  • CS Products
  • Projects
  • Blog
  • About us
  • Contact Us
  • Pick Country

Contact

Construction Specialties Australia
Unit 6, 26 Cosgrove Road
Enfield, NSW 2136
AUSTRALIA
Tel: 1300 272 602
Fax: 1300 247 407
Email: sales@c-sgroup.com.au

Privacy

This website uses cookies to help us give you the best experience when you visit our website. By continuing to use this website, you consent to our use of these cookies. Find out more about how we use cookies and how to manage them below in our privacy policy.
Privacy Policy

Construction Specialties Australia acknowledges the Traditional Custodians of the Lands on which we operate throughout Australia, and recognise their continuing connection to the land, waters and culture. We pay our respects to them and to Elders, past and present.

Copyright © 2025 · Construction Specialties

Copyright © 2025 · Genesis Framework · WordPress · Log in